Introduction

Allgemeines zur HL7 SchnittstelleSchnittstelle  ACK,  


General Data Used

Drübergehen DTM Format?


Key

Not listed fields are ignored

Default configuration - can be confgured in some extent.

Receiving / Sending seen from custo diagnostic perspective

Common Segments

MSH - Segment


Default Usage
MSH-3

Sending Application. 

Receiving: Expected value can be configured (default empty) in custo diagnostic and works as a filter - meaning messages with deviant content in MSH-3 are ignored.

Sending: Sending Application, e.g. "CUSTO" can be configured in custo diagnostic.

MSH-4

Sending Facility

Receiving: Expected value can be configured in custo diagnostic and works as a filter - meaning messages with deviant content in MSH-

3

4 are ignored

. When

Sending: Sending Application, e.g. "CUSTO" can be configured in custo diagnostic. When a tenant system (german "

Mandant

Mandantensystem") is configured, this field contains the information about the tenant. See "Tenant System" below. 

MSH-5

Receiving Application

Receiving: Expected value can be configured (default empty) in custo diagnostic and works as a filter - meaning messages with deviant content in MSH-3 are ignored.

Sending: Receiving Application, can be configured (default empty) in custo diagnostic e.g. "HIS".

MSH-6

Receiving Facility

Receiving:  Expected value can be configured in custo diagnostic and works as a filter - meaning messages with deviant content in MSH-3 are ignored.  When a tenant system (german "Mandantensystem") is configured, this field should contain the information about the tenant. See "Tenant System" below. 

Sending: Receiving Facility, can be configured (default empty) in custo diagnostic e.g. "HIS".

MSH-7Date/Time Of Message, see HL7 Standard.  ##DTM##
MSH-9

Message Type, see HL7 Standard.  By default, custo diagnostic sends Messagetype^Event^Message-Structure, e.g.  ORU^R01^ORU_R01

MSH-10Message Control ID, see HL7 Standard
MSH-12Version ID, see HL7 Standard. Custo diagnostic supports Version 2.3, 2.5






PID - Segment


PV1 - Segment

...

Observation Results (ORU)



Physical Transport