Introduction

Allgemeines zur HL7 Schnittstelle  ACK,  


General Data Used

Drübergehen DTM Format?

""


Key

Not listed fields are ignored

Default configuration - can be confgured in some extent.

Receiving / Sending seen from custo diagnostic perspective


Common Segments

MSH - Segment

Fieldo/rDefault Usage
MSH-3o

Sending Application. 

Receiving: Expected value can be configured (default empty) in custo diagnostic and works as a filter - meaning messages with deviant content in MSH-3 are ignored.

Sending: Sending Application, e.g. "CUSTO" can be configured in custo diagnostic.

MSH-4o

Sending Facility

Receiving: Expected value can be configured in custo diagnostic and works as a filter - meaning messages with deviant content in MSH-4 are ignored. 

Sending: Sending Application, e.g. "CUSTO" can be configured in custo diagnostic. When a tenant system (german "Mandantensystem") is configured, this field contains the information about the tenant. See "Tenant System" below. 

MSH-5o

Receiving Application

Receiving: Expected value can be configured (default empty) in custo diagnostic and works as a filter - meaning messages with deviant content in MSH-3 are ignored.

Sending: Receiving Application, can be configured (default empty) in custo diagnostic e.g. "HIS".

MSH-6o

Receiving Facility

Receiving:  Expected value can be configured in custo diagnostic and works as a filter - meaning messages with deviant content in MSH-3 are ignored.  When a tenant system (german "Mandantensystem") is configured, this field should contain the information about the tenant. See "Tenant System" below. 

Sending: Receiving Facility, can be configured (default empty) in custo diagnostic e.g. "HIS".

MSH-7rDate/Time Of Message, see HL7 Standard.  ##DTM##
MSH-9r

Message Type.  By default, custo diagnostic sends Messagetype^Event^Message-Structure, e.g.  ORU^R01^ORU_R01. 

MSH-10rMessage Control ID, see HL7 Standard
MSH-12r

Version ID, 

Sending: Custo diagnostic supports Version 2.3, 2.5 

##Verhalten bei eingehenden Nachrichten noch prüfen, wenn 2.7  2.9 oder 1.5 o.ä. drin steht##

MSH-13rSequence Number, see HL7 Standard
MSH-15####prüfen, sieh auch DS-840)##
MSH-16####prüfen, sieh auch DS-840)##
MSH-18o

Character Set  ##zu prüfen##

Receiving: see Standard

Sending: By Default empty, ##Tatsächlich verwendetes CodeSet? ???? is used to encode message## 







PID - Segment

### Hier bitte alles aus default Mapping übernehmen.###

z.B.  PID-3,  r, Patient-ID, see HL7 Standard. PID-3-1 is used to identify the patient in custo diagnostic. It must be unique in custo diagnostic system, otherwise an appropriate tenant system must be used (see tenant system below).

Required sind patienten name/vorname, geburtsdatum, Patienten-nummer, geschlecht?, 



Fieldo/rDefault Usage



PID-8r ?

Administrative Sex. Supported Values are F, M, ?? Other Values are interpeted as ... 








PV1 - Segment



Patient Data Logic (ADT)



Tenant System




Orders (ORM)



Observation Results (ORU)



Physical Transport